| Functions |
Simultaneously measures current, voltage, phase, frequency, phase sequence, active power, reactive power, apparent power, power factor, and vector sum of current in three-phase 380V/220V power systems. Identifies transformer wiring groups, inductive/capacitive circuits. Tests secondary circuits and busbar protection systems. Reads phase relationships between CT groups in differential protection. Checks watt-hour meter wiring correctness. Inspects line equipment. |
| Power Supply |
DC 7.4V, 3000mAh rechargeable Li-ion battery, USB charging port. Approx. 10 hours continuous operation when fully charged. |
| Rated Current |
Approx. 180mA Max |
| Display Mode |
3.5-inch TFT-LCD display |
| Dimensions (H×W×D) |
207mm×101mm×45mm |
| Clamp Jaw Size |
φ7.5mm×13mm |
| Sampling Rate |
Approx. 3 times/second |
| Ranges |
AC Voltage: 0.00V~600V |
| AC Current: 0.0mA~30A |
| Phase: 0.0°~360.0° |
| Frequency: 45.00Hz~65.00Hz |
| Active Power: 0.0W~12kW |
| Reactive Power: 0.0VAR~12kVAR |
| Apparent Power: 0.0VA~12kVA |
| Power Factor: -1~+1 |
| Vector Sum of Current: 0mA~60A |
| Resolution |
Voltage: AC 0.01V |
| Current: AC 0.1mA |
| Phase: 0.1° |
| Frequency: 0.01Hz |
| Active Power: 0.1W |
| Reactive Power: 0.1VAR |
| Apparent Power: 0.1VA |
| Power Factor: 0.001 |
| Vector Sum of Current: 1mA |
Accuracy (Reference Conditions)
|
Voltage: ±(0.5% of range) |
| Current: ±(0.5% of range) |
| Phase: ±1° (Operating condition error: ±3° for 10mA~30A; ±5° below 10mA; For current phase accuracy below 5mA, do not measure voltage. For voltage-current phase test, voltage ≥5V and current ≥5mA required for accuracy.) |
| Active Power: ±(1.0% of range) |
| Reactive Power: ±(1.0% of range) |
| Apparent Power: ±(1.0% of range) |
| Frequency: ±(1.0% of range) |
| Power Factor: ±0.03 |
Phase Sequence
|
Positive Sequence: U1, U2, U3 or I1, I2, I3 cursors flash sequentially left to right. |
| Negative Sequence: U1, U2, U3 or I1, I2, I3 cursors flash sequentially right to left. |
| Detection Rate |
Approx. 2 seconds/time |
| Data Hold |
Press HOLD key to hold data, "HD" symbol displayed. |
| Data Storage |
99 groups |
| Charging Port |
USB charging port |
| Auto Power Off |
Powers off automatically after approx. 15 minutes of inactivity to save battery. |
| Backlight |
Yes, adjustable brightness. |
| Voltage Detection |
Low battery symbol displayed when voltage is low, prompting charging. Auto power off within 10s. |
Weight
|
Host: Approx. 447g (with battery) |
| Current Clamps: Approx. 178g×3 |
| Test Leads: Approx. 162g×2 |
| Total Weight: Approx. 1.221kg |
| Test Lead Length |
1.5m |
| Current Clamp Cable Length |
2m |
| Operating Temp. & Humidity |
-10ºC~40ºC; <80% RH |
| Storage Temp. & Humidity |
-10ºC~60ºC; <70% RH |
| Input Impedance |
Test Voltage Input Impedance: 1MΩ |
| Withstanding Voltage |
Withstands 1000V/50Hz sine wave AC voltage between circuit and case for 1 minute. |
| Insulation Resistance |
≥100MΩ between circuit and insulated case. |
| Construction |
Double insulation, with insulated anti-vibration protective cover. |
| Safety Compliance |
IEC61010-1 CAT III 600V, IEC61010-031, IEC61326, Pollution Degree 2 |